Model | M40W-690 | M40W-400 | M40W-230 |
Lightning protection zone(LPZ) | 1-2 | ||
Standards Compliance | IEC61643-11, EN60950 | ||
Classification | Class C/Type 2 | ||
Nominal working voltage Un | 690V | 400V | 230V |
Max continuous operating voltage Uc | 700V | 440V | 250V |
Nominal discharge current (8/20µs) In | 20KA | ||
Max discharge current Imax (8/20µs) Imax | 40KA | ||
Follow current interrupt rating Ifi | 25KArms/100Arms | ||
Short-Circuit Current Rating Isccr | 25KA | ||
Temporary overvoltage (TOV)(L-N) Ut | 440 V / 120 min. – withstand | ||
Temporary overvoltage (TOV) [N-PE) Ut | 1200 V / 200 ms – withstand | ||
Protection level Up | 3000V | 2200V | 1500V |
Response time tA (L-N/N-PE) | 25ns | ||
Protection model | L L L N-PE | L L L-PE | L N-PE |
Dimension | 90 (H)×90(W)×65(L)mm | 90 (H)×54(W)×65(L)mm | 90 (H)×36(W)×65(L)mm |
Mounting | DIN-rail Mounting 35mm | ||
IP code | IP20 | ||
Working conditions | Temperature: -40 to 80℃, Relative humidity: ≤95% |