Model | Frame Class Rated Current(A) | Rated Current(A) | Rated Working Voltage | Rated Voltage(V) | Rated Ultimate Short-circuit Breaking Capacity(kA) | Rated Operating Short-circuit Breaking Capacity(kA) | Fight Distance(mm) | ||
400V | 690V | 400V | 690V | ||||||
JCM1-63L | 63 | 6,10,16,20,25,32,40,50,63 | 400 | 500 | 25 | / | 22 | / | ≤50 |
JCM1-63M | 50 | / | 35 | / | |||||
JCM1-63M/4 | |||||||||
JCM1-100L | 100 | 10,16,20,25,32,40,50,63,80,100 | 400/690 | 800 | 35 | / | 22 | / | ≤50 |
JCM1-100L/4 | |||||||||
JCM1-100M | 50 | 10 | 35 | 5 | ≤50 | ||||
JCM1-100M/4 | |||||||||
JCM1-125L | 10,16,20,25,32,40,50,63,80,100,125 | 400/690 | 800 | 35 | / | 22 | / | ≤50 | |
JCM1-125L/4 | |||||||||
JCM1-125M | 50 | 10 | 35 | 5 | ≤50 | ||||
JCM1-125M/4 | |||||||||
JCM1-225L | 250 | 100,125,160,180,200,225 | 400/690 | 800 | 35 | / | 25 | / | ≤50 |
JCM1-225M | 50 | 10 | 35 | 5 | ≤50 | ||||
JCM1-225M/4 | |||||||||
JCM1-250L | 100,125,160,180,200,225,250 | 400/690 | 800 | 35 | / | 25 | / | ≤50 | |
JCM1-250M | 50 | 10 | 35 | 5 | ≤50 | ||||
JCM1-250M/4 | |||||||||
JCM1-400L | 400 | 225,250,315,350,400 | 400/690 | 800 | 50 | 10 | 25 | 5 | ≤50 |
JCM1-400L/4 | |||||||||
JCM1-400M | 65 | 10 | 42 | 5 | ≤50 | ||||
JCM1-400M/4 | |||||||||
JCM1-630L | 630 | 400,500,630 | 400/690 | 800 | 50 | / | 35 | / | ≤100 |
JCM1-630M | 65 | 10 | 42 | 5 | ≤100 | ||||
JCM1-630M/4 | |||||||||
JCM1-800M | 800 | 630,700,800 | 400/690 | 800 | 65 | 10 | 42 | 5 | ≤100 |
JCM1-1250M | 1250 | 800,1000,1250 | 400/690 | 800 | 65 | 25 | 42 | 12.5 | ≤100 |